Gas Leak Detector RLA 100
Gas
Leak Detector to detect carbon dioxide (CO2) / 2 configurable alarm
thresholds /
4-digit digital display / integrated alarm transmitter / simple wall montage
|
The
gas leak detector RLA 100 is a well-priced device to detect carbon monoxide (CO2).
The gas leak detector RLA 100 prevents heath issues caused by the colorless and inodorous
gas, used in the food industry, metal industry, in chemical processes and in the
waste industry. The gas leak detector consists of two units: the detector is to
be placed within locations with higher risks, while the alarm unit is placed
outside that area. The gas leak detector features two adjustable alarm
thresholds. If the measured value trespasses the pre-set threshold, an alarm is
set-off (alarm lights and alarm-buzzer). The gas leak detector RLA 100 featured
a 4-digit digital display as well as four LED lights assuring a steady visual
monitoring of the gas concentration. Through the accessible, potential-free
change-over contacts you can activate further alarm units, switch-on an
exhauster or stop a machine. The gas leak detector RLA 100 can be easily mounted
to a wall. It consists of a system compartment, a gas detector, an alarm unit
and a cable to connect the gas detector with a remote controlling unit.
Even smaller amounts of carbon dioxide might cause severe effects on the human
organism. A concentration above 0.3 % in the air might effect the health. If the
concentration arises to 5 %, it causes headaches and dizziness, while a
concentration of more than 8 % lead to unconsciousness and even death. If
there are any questions about this
gas leak detector RLA 100, please have a look at the technical specification
below or call: UK customers +44(0) 23 809 870 30 / US customers +1-410-387-7703.. Our engineers and
technicians will gladly advise you regarding the gas
leak detectors
or any
other products in terms of regulation
and control, or scales
and balances of PCE
Instruments.
|
|
|
-
Detection of carbon dioxide (CO2)
- 2 configurable alarm thresholds
- 4 digit digital display
- Steady visual control option
|
-
Potential-free change-over contact
- Integrated alarm
- Easy mounting on wall
- Three system-components
|
General
Technical Specifications of the Gas Leak Detector RLA 100
|
Gas
Detector
|
Measured
gas
|
carbon
dioxide (CO2): 0 ... 50,000 ppm (5%) (vol.) NDIR sensor
|
Temperature
(gas / environment)
|
0
... +45 °C
|
Supply
of gas samples
|
by
diffusion
|
Alarm
contacts
|
-
1 potential-free change-over contactor to control external devices (NO/NC) by
releasing alarm 1
- Switching power: 30 V DC / 250 V AC, max. 2 A
|
Alarm
thresholds
|
alarm
1
0.5 / 1 / 1.5 / 2 %
alarm 2
1.5 / 2 / 2.5 / 3 / 3.5 / 4 %
|
Menu
items
|
Function
test of connection between detection unit and alarm unit, calibration, switch
between °C and °F, alarm 1, 2 and factory setting
|
Display
elements
|
-
4-digit digital display for measured gas concentration within range 0 ... 9999
ppm
- 3-digit digital display for measured gas concentration within range 1 ... 5
%
- additional 3-digit digital display for measurement and temperature in °C
and °F
- LEDs for operation, alarm 1, 2 and monitoring of voltage supply
|
Operating
elements
|
reset,
menu selection, enter
|
Safety
|
Continuous
self-surveillance of temperature range, sensor life-time, unplausible values,
EEPROM system, internal data transfer
|
Enclosure
|
synthetic,
IP 54, splash-water proof
|
Diameters
|
168
x 125 x 47 mm (without connections)
|
Voltage
Supply
|
Adapter
100 ... 240 V AC, 50 / 60 Hz
|
Measuring
unit
|
Temperature
(gas / environment)
|
0
... +45 °C
|
Menu
items
|
-
4-digit digital display for gas concentration within range 0 ... 9999 ppm
- 3-digit digital display for concentration within range 1 ... 5%
- additional digital display to measure temperature in °C and °F
- LEDs for operation, alarm 1, 2 and monitoring of voltage supply
|
Display
elements
|
Function test, reset, menu selection, enter,
shifting between °C and °F
|
Enclosure
|
aluminum,
IP 54, splash water proof
|
Diameters
|
118
x 85 x 34 mm (without connections)
|
Voltage
Supply
|
via
data cable to gas detector
|
Delivery
Content of Gas Leak Detector RLA 100
|
1
x gas leak detector RLA 100
1 x instruction manual
|
|
|
|
Here you will find an overview of all the
measuring instruments available at PCE Instruments. |
Contact: PCE Instruments UK Limited
Unit 11 Southpoint Business Park
Ensign Way, Southampton
United Kingdom, SO31 4RF
Phone: +44(0) 23 809 870 30
Fax: +44(0) 23 809 870 39
|
Contact: PCE Americas Inc.
1201 Jupiter Park Drive, Suite 8
Jupiter 33458 FL
USA
Phone: +1-410-387-7703
Fax: +1-410-387-7714
|