Fuse Indicator(FI/RCD PCE-RCD 1)
Two-pole voltage detector for transit and rotation field indicator / with illumination of the measured point
|
This tester series fuse indicator / RCD 1 determines the current of the trigger and the trigger time of fuse protection switches. The selection of different test currents allows a very flexible use of this tester. In any electric system, there are current leakage protection facilities known as fuses. These protection facilities cut the power supply at the moment it detects a leakage current. The tester passes a leakage current and determines with which leakage current the protection switch reacts. In addition, the fuse indicator measures the reaction time. These two parameters, the trigger current and the trigger time are the relevant security values for a fuse indicator switch. The management of the tester is very simple. In addition to the maximum test current, it can adjust the type of fuse (normal or selective) and whether to measure the trigger current and/or the trigger time. You can also select if the test current must start with a positive or negative half wave. Once you have set all these parameters, you can start the measurement by pressing a single key. The colour of the tester screen allows a quick assessment of whether the system is right or wrong. In the large LCD screen, you can measure the value of measurement. The tester also beeps when input voltage is too large, when there is no ground or when ground potential is greater than 50 V.
We also have another similiar VDE tester but more oriented towards the industrial sector rather than the health sector since this does not comply with the VDE 0751. The following link has an overview where you can find the most appropriate VDE tester for you.
|
|
Tester FI/RCD PCE_RCD 1
|
- Set of test current rom 10 mA to 650 mA - Alarm when exceeding the input voltage maximum, lack of grounding and ground potential above 50 V
|
- Measure the fuse switch trigger time - Status check with the colour screen - EN 61010-1, CAT III 600 V
|
Technical specifications
|
Display
|
3 digits, backlight (blue and red)
|
RCD types
|
Normal or selective RCD
|
Voltage range
|
210 ... 240 V (neuter phase) 50/60 Hz
|
Alarm
|
Input voltage too high, lack of grounding and ground potential above 50 V
|
Environmental temperature
|
Operating: -15 ... +45 ºC Storage: -25 ... +70 ºC
|
Protection type
|
IP 40
|
Weight
|
340 g
|
Dimensions
|
71 x 210 x 51 mm
|
Power supply
|
4 x 1.5 V AA
|
Norms
|
EN 61010-1: CAT III 600 V EN 61557-6 EN 61236 (EMC)
|
|
|
The tester FI/RCD PCE RCD 1 checking the system in a house. Big display for easier use.
|
The screen colour of the tester changes when overpassing the limit values or when not detecting ground.
|
Delivery contents 1 x tester
FI/RCD PCE RCD 1, 1 x user’s manual.
|
|
|
|
Here you will find an overview of all the measuring instruments available at PCE Instruments.
|
Contact: PCE Instruments UK Limited
Unit 11 Southpoint Business Park
Ensign Way, Southampton
United Kingdom, SO31 4RF
Phone: +44(0) 23 809 870 30
Fax: +44(0) 23 809 870 39
|
Contact: PCE Americas Inc.
1201 Jupiter Park Drive, Suite 8
Jupiter 33458 FL
USA
Phone: +1-410-387-7703
Fax: +1-410-387-7714
|