Humidity sensor PCE-P18
Humidity sensor measures temperature and air
humidity / output as standard signal / compact / Modbus RTU interface / wall
fastening
|
The humidity sensor PCE-P18 can be used to monitor air humidity and temperature in HVAC engineering. The humidity sensor PCE-P18 releases the measured indicator as a standard signal 4…20 mA (not galvanic isolated). Air humidity and temperature are detected accurately due to a semiconductor. For operation the humidity sensor PCE-P18 is supplied via direct current. The measuring data is then shown via a two-wire line. All connections are made via screwed-contacts with water-proof IP 65 enclosure. Aside from displaying the signal as a 4…20 mA signal the measuring data can also be read through a RS485 interface. This feature is especially useful if different measuring points are to be connected during your building monitoring. For further information about the humidity sensor PCE-P18 please read the following technical data or use our
contact
form. Our engineers and technicians will gladly advise you regarding the humidity sensor PCE-P18 or any other of
PCE Instruments product in the areas of
regulation and control or
scales and
balances. Here you will find a further
humidity sensor with similar features or an overview of further humidity sensors for various fields of application in industry or research.
|
|
|
-
Humidity- and temperature-sensor
- 4…20mA output
- Simple wall fastening
- RS-485 interface
|
-
For constant monitoring
- Different filters deliverable
- Small measuring
- Modbus RTU
|
Technical data humidity sensor PCE-P18
|
Humidity
|
Measuring range
|
0 ... 100 %RH
|
Accuracy
|
± 2 % (for range of 10 % .... 90 %
RH)
± 3 % (residual range)
|
Hysteresis
|
± 1 % RH
|
Temperature
|
Measuring range
|
- 20 ... 60 °C
|
Accuracy
|
± 0.5 % of measuring range
|
Temperature influence
|
± 25 % / 10 °C
|
Output humidity sensor
|
Electricity
|
4 ... 20 mA
|
Maximum suitable resistance at output
|
≤ 500 Ω
|
Data interface
|
RS-485 Modbus RTU
|
Mode of transmission
|
8N1, 8N2, 8E1, 8O1
|
Signal rate
|
4800 Bit/s
9600 Bit/s
19200 Bit/s
38400 Bit/s
57600 Bit/s
|
General technical data humidity sensor
|
Voltage supply
|
19 V ... 30 V DC
|
Power
|
< 1.5 W
|
Surrounding temperature
|
- 30 °C ... 85 °C
|
Max. air humidity
|
≤ 95 % RH
|
Preheating time
|
15 minutes
|
Protection grade
|
IP 65
|
Montage
|
wall montage
|
Measures (AxHxD)
|
35 x 58 x 118 mm
|
Weight
|
125 g
|
4 ... 20 mA Interfaces
|
Both 4…20mA interfaces are not isolated galvanic from one another. To use both signals we advise you to use the signal converter PCE-P171
|
Delivery content:
|
1 x temperature converter PCE-P18, 1 x instruction manual
|
Available
variations of humidity sensor PCE-P18
|
Humidity sensor PCE-P18-1
|
RS-485 Modbus Interface
|
Humidity sensor PCE-P18-2
|
RS-482 Modbus interface with 4…20 mA output
|
Additional equipment for temperature converter PCE-P18
|
|
Diaphragm filter
PTFE laminated synthetic enclosure, porosity: 1 µm, temperature: max. 80° C, Reaction time up to T90: 15 s, for interiors with low contamination
|
|
PTFE filter
PTFE, sintered, porosity: 50 µm, temperature: max. 180° C, reaction time up to T90: 14 s, for application in chemistry
|
|
Sinter
filter
bronze, sintered, porosity: 60 µm, reaction time up to T90: 10 s, for application in high pollution, protection against mechanic damage
|
|
|
Here you will find an overview of all the measuring instruments available at PCE Instruments. |
Contact: PCE Instruments UK Limited
Unit 11 Southpoint Business Park
Ensign Way, Southampton
United Kingdom, SO31 4RF
Phone: +44(0) 23 809 870 30
Fax: +44(0) 23 809 870 39
|
Contact: PCE Americas Inc.
1201 Jupiter Park Drive, Suite 8
Jupiter 33458 FL
USA
Phone: +1-410-387-7703
Fax: +1-410-387-7714
|