Mounting
Wattmeter PCE-ND10
Mounting wattmeter for permanent installation / Lighted
3.5 " display / 2 alarm outputs / impulse output / Modbus RTU interface /
IP 656 front / phase recognition /
measurement and display of power, voltage, power rating, efficiency factor,
phase angle...
|
The
mounting wattmeter PCE-ND10 measures all system parameters 3-phase. Electricity,
voltage and power determination are an easy task for the mounting wattmeter
PCE-ND10. The electricity measurement can be determined via the mounting
wattmeter directly and 3-phase. But there is also the possibility of measuring
higher currents by means of transducers in
combination with the mounting wattmeter PCE-ND10. The voltage metering is
performed directly up to 500 V (phase-to-phase) due to the connections at the
mounting wattmeter. The mounting wattmeter PCE-ND10 is entirely designed for
operation in 3-phase networks. All measured parameters are shown on a large, lighted
display. Via the buttons placed at the front the user is enabled to scroll
through the parameters and feed-in all relevant settings for the measurement via
the mounting wattmeter. Furthermore the mounting wattmeter is equipped with
alarm-relays which signalize an exceed or undershoot of the preset parameters.
Due to the Modbus RTU interface of the mounting wattmeter the recorded values
can be transferred. By means of the impulse output the mounting wattmeter
PCE-ND10 can transfer the active energy to an energy meter/ electricity meter.
The front of the mounting wattmeter PCE-ND10 is protected according to IP67. The
mounting wattmeter is to be installed into switch panels. The extract measures
92 x 92 mm. The dimensions of the mounting wattmeter's front measure 96 x 96 mm.
If there are any questions about this
mounting wattmeter PCE-ND10, please have a look at the
technical specification below or call: UK customers +44(0) 23 809 870 30 / US customers +1-410-387-7703. Our technicians and engineers will gladly advise you in all energy
meters and all products in the field of measuring
instruments, regulation
and control and scales.
|
|
|
-
Extract from switch panel 92 x 92 mm
- Measuring: U, I, f, P, Q, S, PF...
- Feed-in through measuring voltage
- Alarm function
- Recognition of false phase order
|
-
Impulse output of active energy
- IP 65 front-sided
- lighted 3.5" LC display
- Simple installation
- RS485 Modbus interface
|
Technical Specifications
|
Measured
indicator
|
Display
range
|
Measuring
range
|
Accuracy
|
Power
In
|
1A
|
0.00
... 1500 A
|
0.005
... 1.2 A AC
|
±
0.2 % from range
|
5A
|
0.00
... 60000 A
|
0.025
... 6 A AC
|
|
Voltage
L-N
|
230
V
|
0.0
... 1.012 MV
|
195
... 253 V AC
|
±
0.2 % from value
|
290
V
|
0.0
... 1.200 MV
|
246
... 300 V AC
|
|
Voltage
L-L
|
400
V
|
0.0
... 1.752 MV
|
340
... 440 V
|
±
0.5 % from value
|
500
V
|
0.0
... 2.000 MV
|
425 ... 520 V
|
|
Frequency
|
47.0
... 63.0 Hz
|
47.0
... 63.0 Hz
|
±
0.2 % from value
|
Active
power
|
-9999
... 9999 MW
|
-1.52
kW ...1.52 kW
|
±
0.5 % from range
|
Reactive
power
|
-9999
... 9999 Mvar
|
-1.52
... 1.52 Mvar
|
±
0.5 % from range
|
Apparent
power
|
0.00
VA ... 9999 MVA
|
1.0
VA ... 1.52 VA
|
±
0.5 % from range
|
Power
factor PF
|
-1
... 1
|
-1
... 1
|
±
1 % from range
|
Tan
φ
|
-1.2
... 1.2
|
-1.2
... 1.2
|
±
1 % from range
|
Cos
φ
|
-1
... 1
|
-1
... 1
|
±
1 % from range
|
φ
|
-180
... 180 °
|
-180
... 180 °
|
±
0.5 % from range
|
Absorbed
active energy
|
0
... 99,999,999 kWh
|
|
±
0.5 % from range
|
Released
active energy
|
0
... 99,999,999 kWh
|
|
±
0.5 % from range
|
Absorbed
reactive energy
|
0
... 99,999,999 kWh
|
|
±
0.5 % from range
|
Released
reactive energy
|
0
... 99,999,999 kWh
|
|
±
0.5 % from range
|
THD
|
0
... 100 %
|
|
±
5 % from range
|
General
technical specifications
|
Relay
output
|
2
outputs, max. 250 V AC/ 0.5 A
|
Impulse
output active power
|
O/C (NPN),
class A according to EN62053-31,
voltage 18 ... 27 V,
power 10 ... 27 mA
|
RS485
interface
|
Modbus
RTU 8N2 / 8E1 / 8 O1 / 8n1
baud rate 4800 / 9600 / 19200 / 38400 bit/ s
|
Display
|
monochrome
3.5 " LCD, leighted
|
Supply
voltage from L3
|
195 ... 253
V AC / 47 ... 62 Hz
246 ... 300
V AC / 47 ... 62 Hz
|
Surrounding
conditions
|
-20
... 55 °C / 25 ... 95 % rH
|
Storage
conditions
|
-
30 ... 70 ° C / non-condensing
|
Electrical
security
|
EN
61010-1
|
Dimensions
|
96
x 96 x 77 mm
|
Switch
panel extract
|
92
x 92 mm
|
Weight
|
approx.
300 g
|
Protection
type
|
IP65
|
|
Delivery
content
|
1x
mounting wattmeter PCE-ND10, 2 x connection clamps, 1 x instruction manual
|
Delivery
of varieties:
|
PCE-ND10-1
|
Power
input: 1 A
Voltage input: 230 V/ 400 V
without RS485 interface
|
PCE-ND10-2
|
Power
input: 5 A
Voltage input: 230 V/ 400 V
without RS485 interface
|
PCE-ND10-3
|
Power
input: 1 A
Voltage input: 230 V/ 400 V
with RS485 interface
|
PCE-ND10-4
|
Power
input: 5 A
Voltage input: 230 V/ 400 V
with RS485 interface
|
PCE-ND10-5
|
Power
input: 1 A
Voltage input: 290 V/ 500 V
without RS485 interface
|
PCE-ND10-6
|
Power
input: 5 A
Voltage input: 290 V/ 500 V
without RS485 interface
|
PCE-ND10-7
|
Power
input: 1 A
Voltage input: 230 V/ 400 V
with RS485 interface
|
PCE-ND10-8
|
Power
input: 5 A
Voltage input: 290 V/ 500 V
with RS485 interface
|
|
|